qiao@hvtest.cc15871365102
  • Penganalisis Karakteristik Volt-ampere PT UHV-300 CT

    UHV-300 CT PT Volt-ampere Characteristic Analyzer adalah instrumen uji profesional untuk transformator di industri tenaga listrik dan mengadopsi DSP dan ARM berkinerja tinggi, proses manufaktur yang canggih

    Detail Produk Penganalisis Karakteristik Volt-ampere PT UHV-300 CT


    Introduction

    The UHV-300 CT PT Tester is used for testing both current transformers (CT) and voltage transformers (VT). It performs key measurements such as the excitation characteristics and excitation parameters of instrument transformers. Additionally, it is capable of conducting turns ratio tests, polarity checks, and winding resistance measurements on transformer coils. Specifically for voltage transformers, it is employed for excitation characteristic testing, PT turns ratio verification, and PT polarity inspection.


    The main parameters

    UsageProtection CT, protection PT
    Keluaran0~180Vrms,12Arms,18A(Peak)
    Akurasi pengukuran tegangan±0.2%
    Pengukuran rasio CTRange:1~40000
    Accuracy: ±0.2% ±0.05% (customizable)
    Pengukuran rasio PTRange:1~40000
    accuracy:±0.2%
    Pengukuran faseThe resolution of the:0.5min
    accuracy:±5min
    Pengukuran resistansi belitan sekunderRange:0~300Ω
    accuracy:2%±2mΩ
    Pengukuran beban ACRange:0~300VA
    accuracy:2%±0.2VA
    Sumber Daya listrikAC220V±10%,50Hz
    Lingkungan kerjaTemperature: -10℃ ~ 50℃, humidity: ≤90%
    Dimensi dan beratsize:340mm×220mm×330m,The weight of the:≤9kg


    Characteristics

    1、Full-featured, not only satisfy the test requirements of various CTs (include TP class), such as the excitation characteristics (i.e., volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary burden, ratio error and phase displacement, but can also be used for the tests of various PTs, including excitation characteristics of the electromagnetic unit, ratio, polarity, secondary winding resistance, ratio error and phase displacement.
    2、 Automatically give CT, VT parameters, including knee point voltage / current, 10% error curve, the accuracy limit factor (ALF), instrument security factor (FS), the second time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductance etc.
    3、Test meet IEC60044 GB1208 (-1) GB16847 (IEC60044-6) became etc all kinds of transformer standards, and in accordance with the transformer types and levels of automatic choose which standard test.
    4、Based on the advanced low-frequency method to test principle of, it can deal with CT test with inflection point up to 30kV.
    5、Interface friendly and beautiful, Chinese graphics interface.
    6、The device can store 2000 sets of test data without loss when power is lost.After the test, use U disk to store it on the PC, analyze the data with the software, and generate WORD report.
    7、The test is simple and convenient. The direct resistance, excitation, ratio change and polarity tests of CT are completed with one key. Besides the load test, all other tests of CT adopt the same wiring mode.
    8、Easy to carry, device weight<9kg.







    Anda Mungkin Juga Menyukainya

    • Ada pertanyaan!

      JANGAN RAGU UNTUK MENGHUBUNGI KAMI SETIAP SAAT
      Hubungi kami
    • Kunjungi kami

      Gedung 6, Taman Industri Optik-Mekanis Lembah Optik, Jalan 84 Gaoxin 5,
      Zona Pengembangan Teknologi Baru East Lake, Kota Wuhan, Provinsi Hubei, Tiongkok

    • Email Kami

      qiao@hvtest.cc

    • Hubungi Kami

      +86-15871365102