Product Introduction
The Six Phase Relay Protection Tester is a new miniaturized microcomputer relay protection tester based on DL/T 624-2023 "Technical Conditions for Microcomputer Relay Protection Test Equipment" issued by the Ministry of Electric Power. It has widely listened to user opinions, summarized the advantages and disadvantages of similar domestic products, and fully utilized modern advanced microelectronics technology and devices. The flexible combination of voltage and current output can reach up to 6-phase voltage and 6-phase current, and can be freely combined to achieve traditional 4-phase voltage, 3-phase current type, 6-phase voltage type, 6-phase and 12-phase output modes. It is not only compatible with various traditional testing methods, but also convenient for differential testing of three-phase transformers and rapid cutting off and preparation of plant power for self injection testing.
Product Features
1. Versatile Power Output Configuration
- Standard 4-phase voltage (120V/phase) & 3-phase current (120A/phase) outputs 
- Flexible combinations for diverse protection testing requirements 
- Multifunctional 4th voltage channel (Ux) configurable as 3U0 or custom voltage 
2. Intuitive User Interface
- Integrated trackball mouse and optimized keyboard 
- Large TFT LCD display with Chinese Windows OS 
- Ready-to-use upon startup with simplified operation 
3. Dual Control Modes
- Standalone panel operation 
- External PC control (full feature parity) 
- Seamless switching between operation modes 
4. Advanced Linear Amplification Technology
- High-fidelity modular linear amplifiers (non-switching type) 
- Eliminates high/medium frequency interference 
- Maintains waveform integrity across all current ranges 
5. High-Performance Portable Unit
- DSP-controlled output for precise signal generation 
- Compact, lightweight design (under XX kg) 
- Fast startup for immediate field testing 
6. Comprehensive Test Software
- Automated complex verification procedures 
- Protection setting verification 
- Fault simulation and replay 
- Real-time data logging and vector display 
- Instant report generation 
7. Dual DC Power Outputs
- Adjustable 110V/220V DC auxiliary power 
- Independent power supply for external devices 
8. Expanded Connectivity Options
- Dual USB and RS232 interfaces 
- Supports external keyboard/mouse 
- PC communication capabilities 
9. Robust Protection System
- Optimized thermal management 
- Power soft-start circuitry 
- Comprehensive hardware/software safeguards 
- Automatic fault diagnosis and lockout 
Product Parameters
| Current channel number | Standard 6 phase | 
| Voltage channel number | Standard 6 phase | 
| AC current output range | 30A/phase or 180A (six parallel) | 
| DC current output range | 10ADC/phase | 
| AC voltage output range | 120VAC/phase | 
| DC voltage output range | 160VDC/phase | 
AC current output
| 6 phase current output per phase (effective value) | 0 ~ 30A output precision 0.2 | 
| 3 phase current output per phase (effective value) | 0~60A | 
| 6 phase parallel current output (RMS) | 0~180A | 
| Phase current long-term allowable working value (RMS) | 10A | 
| Maximum output power of phase current | 300VA | 
| 6 phase parallel current maximum output power) | 1000VA | 
| 6 Allowable working time for maximum output of phase parallel current | 10s | 
| Frequency range (fundamental) | 0~1000Hz | 
| Harmonic frequency | 1~20 | 
DC current output
| Current output | 0 ~ ±10A/phase output accuracy 0.5 level | 
| Maximum output load voltage | 20V | 
AC voltage output
| Phase voltage output (RMS) | 0 ~ 120V output precision 0.2 | 
| Line voltage output (RMS) | 0~240V | 
| Phase voltage/line voltage output work | 80VA/100VA | 
| Frequency range (fundamental) | 0~1000Hz | 
| Harmonic frequency | 1~20 | 
DC voltage output
| Phase voltage output amplitude | 0 ~ ±160V output accuracy 0.5 | 
| Line voltage output amplitude | 0~±320V | 
| Phase voltage/line voltage output power | 70VA/140VA | 
Switching value
| 8switch inputs | Null contact 1 ~ 20mA, 24V | 
| Potential contact access "0" : 0 ~ +6V; 1: +11 V to +250 V | |
| 4 pairs of switching output | DC:220 V/0.2 A;AC:220 V/0.5 A | 
Time measuring range
| Time measuring range | 0.1ms ~ 9999s | 
| Measurement accuracy | 0<0.1mS | 
| Volume | 375×350×180 (mm3) | 
| Unit weight | 17kg | 
 
   
   
  
  
  
  

 











 
                     
                     
                 
             
             
             
            